1 Question 1 Single choice Fundamentals of Power
A data centre in a region with frequent short voltage sags runs a 480 V three-phase feed to a row of UPS-backed racks. Facilities measured the real power drawn by the IT load at 360 kW while the apparent power at the switchboard is 450 kVA. The operations manager wants to size the new PDU transformer and asks what the power factor is so the cabling and breaker ratings can be checked. Which statement best describes the situation and the correct next step?
Correct Answer: BExplanationPower factor is real power divided by apparent power, here 360 kW over 450 kVA, giving 0.8. Conductors, transformers and breakers carry current governed by apparent power, so they must be sized to the 450 kVA figure rather than the 360 kW real load. Reactive power still produces current and heating, so sizing on real power alone understates the requirement. A power factor above 1 is physically impossible for a passive load, and the 0.5 figure comes from inverting the ratio incorrectly, which would wrongly drive an unnecessary upgrade.
-
2 Question 2 Multiple choice Generator Management
A colocation site has a diesel standby generator that failed to pick up load during a utility outage because its battery-powered starting system was flat. Engineers found that the battery charger had been tripped for months and that the fuel polishing filters were overdue for replacement. The site must restore dependable automatic start-up and reduce the chance of fuel-related stalls during the next outage, with no budget for a new generator. Which two actions best meet these requirements? (Choose two.)
Correct Answer: B, EExplanationThe starting failure traces to a discharged battery bank caused by a tripped charger, so restoring the charger and load-testing the batteries directly addresses automatic start capability. Fuel filters and water separators keep injectors and the engine supplied, so replacing them and checking the day tank removes the fuel-related stall risk. Coolant concentration does not improve battery-driven cranking, and a larger output breaker does not fix a start failure. Replacing the transfer switch with manual changeover would remove the automatic start-and-transfer requirement the site must meet.
-
3 Question 3 Order list Fundamentals of Security
A managed data centre has received a request from a regulated client to add a dedicated caged suite with badge-controlled entry and a logged visitor process, and the client's auditor has requested evidence that access rights were verified before go-live. Facilities has the card reader hardware on site and the client's authorised personnel list in hand. Arrange the steps in the correct order.
Drag the steps into the correct order, or use the arrows.
- Configure the access control system to grant the suite doors only to the enrolled badge holders.
- Verify the client's approved personnel list against identity documents at a supervised enrolment.
- Test a denied-access scenario and a valid entry to confirm the controls work and are logged.
- Assign each authorised person a badge with access limited to the caged suite.
- Record the physical asset inventory of the racks and equipment inside the suite.
Correct Answer:- Assign each authorised person a badge with access limited to the caged suite.
- Record the physical asset inventory of the racks and equipment inside the suite.
- Verify the client's approved personnel list against identity documents at a supervised enrolment.
- Configure the access control system to grant the suite doors only to the enrolled badge holders.
- Test a denied-access scenario and a valid entry to confirm the controls work and are logged.
ExplanationAssets must be identified first so the protection scope is known before any access rules are written. Identity is then verified against the approved list before any credential is issued, which is what the auditor needs as evidence. Badges are issued only after verification, the access control policy is configured against those enrolled holders, and the controls are finally tested for both denial and valid entry. Configuring the reader before verifying identities would grant access to unvetted people, and testing before configuration would produce no meaningful result.
-
4 Question 4 Drag and drop Cooling Layouts for Data Center
A co-location operator is planning a retrofit of a 300 kW hall where racks are arranged in hot and cold aisles but hot exhaust is recirculating over the top of the rack rows, and the operator cannot add floor space or change the chilled water plant. Each requirement below should be matched to the cooling measure that best satisfies it. Match each requirement to the measure that meets it.
Drag each item onto its matching target. On a phone: tap an item, then tap a target.
Deliver cold air to the intake of each cabinet at a consistent temperature without relocating the chilled water plantStop hot exhaust air from looping back over the top of the rack rows into the cold aislePrevent unused rack spaces from letting hot air pass through the cabinet to the cold aisleUpgrade the chilled water supply to a lower set point throughout the buildingPosition perforated floor tiles in front of rack intakesRelocate the computer room air handlers to the ceiling plenumInstall hot aisle containment with a roof panelFit blanking panels in empty rack unitsCorrect Answer:- Stop hot exhaust air from looping back over the top of the rack rows into the cold aisle → Install hot aisle containment with a roof panel
- Prevent unused rack spaces from letting hot air pass through the cabinet to the cold aisle → Fit blanking panels in empty rack units
- Deliver cold air to the intake of each cabinet at a consistent temperature without relocating the chilled water plant → Position perforated floor tiles in front of rack intakes
ExplanationRecirculation over the top of the rows is stopped by a containment roof that separates hot exhaust from the cold aisle, which the existing layout permits without new floor space. Blanking panels close the unused rack units that allow hot air to bypass the equipment and mix into the cold aisle. Perforated tiles placed in front of intakes ensure cold supply reaches each cabinet at a consistent temperature while the plant stays unchanged. The two extra targets change the water plant or the air handler layout, which the operator has ruled out.
-
5 Question 5 Dropdown Fundamentals of Power
A facility manager is reviewing a power distribution plan for a new cage with eight 16 A single-phase outlets on a 230 V supply. The circuit must remain within the 80 percent continuous loading rule and the breaker must be sized accordingly. Complete the sizing statement by selecting the correct value for each blank.
Choose the correct value for each blank.
A 16 A outlet on a 230 V circuit can supply a continuous maximum of A, so the branch breaker should be rated at A, and the cage design must not exceed kW of continuous load on that branch.Correct Answer:A 16 A outlet on a 230 V circuit can supply a continuous maximum of 12.8 A, so the branch breaker should be rated at 20 A, and the cage design must not exceed 3.68 kW of continuous load on that branch.
ExplanationApplying the 80 percent continuous loading rule to the 16 A outlet gives 12.8 A of continuous current. The branch breaker is then rated at the next standard size that covers that load, which is 20 A, rather than 16 A, which would trip under sustained use. At 230 V, 16 A produces 3.68 kW, so 3.68 kW is the continuous maximum. Simply using the full 16 A ignores the continuous loading rule, and choosing 25 A or higher oversizes the breaker and could allow the outlet to be overloaded before the protection operates.
-
6 Question 6 Single choice Generator Management
A data centre's emergency generator is rated for a standby duty and has been tested monthly at no load. During a recent three-hour utility outage the engine began to show black smoke and rising exhaust temperatures after being loaded to 40 percent for the first time in a year. The operator must restore reliable performance for the next outage without replacing the engine. Which maintenance action is the most appropriate first step?
Correct Answer: AExplanationMonthly no-load running does not bring the engine to operating temperature or burn off deposits, which is why the smoke and rising exhaust temperature appeared once real load was applied. A load bank test at a sustained high proportion of rated capacity is the standard method to clean the engine and prove the cooling and fuel systems under realistic conditions. Replacing the engine would break the constraint against replacement. Extending no-load runs does not produce the sustained combustion temperatures needed to clear deposits, and altering injection timing without diagnosis risks worsening the fault.
-
7 Question 7 Multiple choice Fundamentals of Security
A colocation provider is reviewing the physical security of a suite containing a financial client's high-value servers. An internal audit found that staff hold doors open for colleagues, that badge readers log entry but do not require a second factor, and that the perimeter fence has a gap near a loading bay that is monitored only by a camera with no recording. The client's contract requires strong authentication at the suite door and detection of unauthorised presence in the loading bay. Which two actions best satisfy these requirements? (Choose two.)
Correct Answer: C, DExplanationThe contract calls for strong authentication, and a second factor such as a PIN or biometric at the suite door adds that assurance beyond the badge alone. Continuous recording with motion alarms on the loading bay camera provides real detection of unauthorised presence, which the existing unrecorded camera cannot give. A mantrap is a strong control against tailgating, but it does not add authentication strength or loading bay detection, so it answers only part of the problem. A shared keypad combination weakens authentication, and warning signs deter rather than detect.
-
8 Question 8 Single choice Cooling Layouts for Data Center
A hosting company's room houses 40 racks with a combined heat load of 180 kW and uses an air-cooled self-contained unit with an integrated condenser in the room. Engineers note that the condenser discharge air is recirculating back into the intake of the unit because the unit sits against a wall with only 300 mm of clearance. The company wants to restore rated capacity without relocating the room or adding a new unit. Which correction is the most appropriate?
Correct Answer: AExplanationA self-contained unit with an integrated air-cooled condenser depends on fresh air reaching the condenser coil, and recirculation from inadequate clearance raises the intake temperature and cuts capacity. Restoring the manufacturer's clearance, or ducting the discharge clear of the intake, removes the recirculation path without new equipment. Raising fan speed moves more air but does not solve recirculation at the intake. Replacing the condenser type would add infrastructure the company has ruled out, and lowering the set point treats the symptom while the unit keeps drawing its own hot discharge.
-
9 Question 9 Order list Fundamentals of Power
A facility has a 400 kVA UPS feeding a critical bus and a data centre team needs to verify that a power failure is handled without dropping load. The team has the batteries, the bypass switch and the load bank available for testing during a maintenance window. Arrange the steps in the correct order.
Drag the steps into the correct order, or use the arrows.
- Record the battery runtime and compare it with the design requirement before closing the maintenance window.
- Confirm battery charge and runtime readings before any test is started.
- Transfer the critical load to the static bypass and confirm the UPS output is still stable.
- Restore the input supply and check that the rectifier returns to float charge and the UPS is back on normal mode.
- Simulate a utility failure by opening the input feed and observe battery discharge on the load.
Correct Answer:- Confirm battery charge and runtime readings before any test is started.
- Transfer the critical load to the static bypass and confirm the UPS output is still stable.
- Simulate a utility failure by opening the input feed and observe battery discharge on the load.
- Restore the input supply and check that the rectifier returns to float charge and the UPS is back on normal mode.
- Record the battery runtime and compare it with the design requirement before closing the maintenance window.
ExplanationBattery condition must be confirmed before any test, because a discharged battery would make the simulation meaningless and risk the load. Moving the load to static bypass first protects the critical bus during the test and is the safe sequence before opening the input. The utility failure is then simulated and battery discharge observed, after which the input is restored and rectifier float charge verified. Runtime is recorded last against the design requirement, which is only valid once the system has returned to normal operation.
-
10 Question 10 Drag and drop Generator Management
A facility operator has a standby generator set and an automatic transfer switch serving a critical distribution board. During a planned audit the team must confirm that each component of the generator and switchgear works as intended. Match each requirement below to the component or measure that satisfies it. Match each requirement to the item that meets it.
Drag each item onto its matching target. On a phone: tap an item, then tap a target.
Ensure that the generator output is regulated to a stable voltage under changing loadEnsure that the transfer to generator supply occurs only after the utility has failed and the generator is readyProtect the generator frame and enclosure so that a fault current has a low-impedance path to earthFuel day tank level indicatorEquipment grounding conductor bonded to the frameAutomatic voltage regulatorBattery float charger output monitorAutomatic transfer switch sensing and transfer logicCorrect Answer:- Ensure that the generator output is regulated to a stable voltage under changing load → Automatic voltage regulator
- Ensure that the transfer to generator supply occurs only after the utility has failed and the generator is ready → Automatic transfer switch sensing and transfer logic
- Protect the generator frame and enclosure so that a fault current has a low-impedance path to earth → Equipment grounding conductor bonded to the frame
ExplanationThe automatic voltage regulator holds the generator output within its voltage band as load varies, which is its job in the generator set. The transfer switch's sensing and transfer logic controls changeover, waiting for the utility failure and generator readiness before connecting the load. The equipment grounding conductor bonded to the frame provides the low-impedance fault path that protects personnel and allows protective devices to operate. The fuel level indicator and battery charger monitor are useful for operations but do not regulate voltage, control transfer, or provide the earth fault path.
-
11 Question 11 Dropdown Cooling Layouts for Data Center
A data centre engineer is documenting a raised-floor airflow design for a 12-rack hot-aisle and cold-aisle row. The cold aisle must receive air at the intake temperature the rack vendor specifies, and the floor tile plan must avoid unbalanced pressure. Complete the design note by selecting the correct value for each blank.
Choose the correct value for each blank.
Cold aisle supply air should be delivered through floor tiles placed in front of each rack intake, the cold aisle should be kept at a positive pressure relative to the hot aisle by ensuring the perforated tile total open area does not exceed of the plenum supply capacity, and the hot aisle exhaust should be returned to the cooling units through return path.Correct Answer:Cold aisle supply air should be delivered through perforated floor tiles placed in front of each rack intake, the cold aisle should be kept at a positive pressure relative to the hot aisle by ensuring the perforated tile total open area does not exceed 100 percent of the plenum supply capacity, and the hot aisle exhaust should be returned to the cooling units through a dedicated overhead return path.
ExplanationPerforated tiles placed in front of each rack intake put cold air exactly where the intake needs it, which is the purpose of the tile plan. Balancing the total open area against the plenum supply capacity keeps the cold aisle at positive pressure and avoids tiles starving or flooding the floor, so 100 percent is the balanced limit used in the design note. Hot exhaust is returned through a dedicated overhead path to the cooling units so it does not mix back into the cold aisle. The other options either use solid tiles that block airflow or open paths that short-circuit the layout.
-
12 Question 12 Single choice Fundamentals of Security
A managed services provider runs a secure room for a government client that stores classified backup media. The client requires that no single staff member can both approve and execute a media release, and that every access event be reviewed by someone outside the operating team. The provider wants the least costly change that satisfies both conditions using its existing access control system. Which measure is the best choice?
Correct Answer: DExplanationDual authorisation enforces separation of duties by requiring two different credentials at the release point, which the existing access control system can apply without new hardware. Having the compliance team review the logs gives independent oversight outside the operating team, meeting the second condition. A master badge held by a single supervisor breaks the separation of duties requirement, and live camera monitoring by the same operations team does not remove the conflict of interest. Shorter badge expiry does not address either requirement and reviews only at month end, which is too late.
-
13 Question 13 Multiple choice Generator Management
A colocation site is preparing a generator room for an inspection after a complaint about exhaust and noise near residential neighbours. The inspection has highlighted that the generator exhaust silencer has corroded and that the battery cabinet lacks ventilation, while the generator maintenance log shows monthly load bank tests were not recorded for the past year. The operator must restore compliance and maintain availability through the next season. Which two actions best meet these requirements? (Choose two.)
Correct Answer: A, DExplanationReplacing the corroded silencer restores the noise and exhaust control the regulator requires, and checking the readings against the local limits demonstrates compliance rather than assuming it. Adding battery cabinet ventilation addresses the gas accumulation risk, and documenting it against the manufacturer's requirement provides the record the inspection needs. Moving the room is not a realistic fix for a fixed site and does not address the corrosion or ventilation. Removing the batteries would stop the generator from starting, and halting testing removes the evidence of maintenance and creates a new compliance gap.
-
14 Question 14 Single choice Fundamentals of Power
A data centre is designing a 415 V three-phase distribution board that will feed a mix of single-phase servers and three-phase cooling units. The electrical engineer needs to balance the single-phase loads across the three phases so that the neutral current stays within the design limit and the transformer is not overloaded. Which action best achieves this?
Correct Answer: AExplanationDistributing single-phase loads evenly across the three phases keeps the currents close to balanced, which keeps the neutral current low and avoids overloading any one phase of the transformer. Verifying the phase currents under representative load confirms the balance in operation, not just on paper. Concentrating the load on one phase produces a large unbalanced neutral current, and replacing three-phase cooling units with single-phase units is an unnecessary redesign. Bonding the neutral to earth at the board is wrong, because neutral and protective earth must be kept separate at the load side and unbalanced current must return through the neutral, not earth.
-
15 Question 15 Single choice Fundamentals of Security
A colocation provider hosts a mid-sized bank's trading racks in a room where tailgating incidents have been recorded at the main door. The bank's compliance team requires that every entry be attributable to a named individual and that the entry record survive a badge-cloning attack. The facility already has a card reader at the door. Budget is limited and the building owner will not allow new doors to be installed. Which measure best meets the requirement at the lowest additional cost?
Correct Answer: BExplanationA PIN keypad on the existing reader adds a second factor so that a cloned badge alone cannot open the door, and each entry is tied to a person who knows the PIN, which satisfies attribution without structural work. A mantrap would require new construction, which the building owner has ruled out. A turnstile with swipe counting does not stop a tailgater who walks through during an open cycle and does not authenticate the person. Continuous cameras record events but do not prevent tailgating or prove identity at the point of entry.
These are 15 of the 40 questions in the full CDCS-001 pack.
Get All 40 QuestionsGet all 40 questions & answers
Full access options for GAQM CDCS-001
Self-study
PDF Version
- 40 actual exam questions
- Compatible with all devices
- Printable PDF format
- No download limits
- 90 days free updates
- 24/7 customer support
Best value
Bundle Pack
- Discounted PDF + online access
- 40 actual exam questions
- Both PDF and online practice test
- Free 90 days updates
- No download or practice limits
- 24/7 customer support
Exam simulation
Online Practice Test
- 40 actual exam questions
- Actual exam environment
- 90 days free updates
- Browser-based software
- 24/7 customer support
100% Money Back Guarantee
Your success comes first
At DumpsProvider, we give you a 100% money back guarantee on all of our exam dumps. For us, your success is the #1 priority and we are more than confident that our exam material will help you pass the CDCS-001 Exam (Certified Data Centre Specialist) on your very first attempt.
In a rare case, if you fail your exam, we will refund your amount without asking a single question.